Mô tả sản phẩm
sens:Control – safe control solutions
Safety-related parameters
Safety integrity level |
SIL3 (IEC 61508)
SILCL3 (EN 62061)
|
Category |
Category 4 (EN ISO 13849) |
Performance level |
PL e (EN ISO 13849) |
B10d parameter |
1.26 x 106 switching cycles (AC-15, 230 V, I = 1.5 A)
5.9 x 106 switching cycles (AC-15, 230 V, I = 0.75 A)
4.35 x 105 switching cycles (DC-13, 24 V, I = 2.5 A)
1 x 107 switching cycles (DC-13, 24 V, I = 0.63 A)
|
PFHD (mean probability of a dangerous failure per hour) |
3.0 x 10-8 (EN ISO 13849) |
TM (mission time) |
20 years (EN ISO 13849) |
Stop category |
0 (EN 60204-1) |
Interfaces
Connection type |
Fixed screw terminals |
Number of enable current (N/O) contacts |
2, relevant for safety |
Electrical data – Operating data
Voltage supply |
A1, A2 |
Output circuit > 25 V AC / 60 V DC |
PELV |
Output circuit ? 25 V AC / 60 V DC |
PELV or SELV |
|
Supply voltage Vs |
A1, A2 |
|
24 V AC/DC (20.4 V AC/DC … 26.4 V AC/DC) |
|
Residual ripple |
? 2.4 Vpp 1) |
Power consumption |
(? 4.6 VA (AC))
(? 2.1 W (DC))
|
Overvoltage category |
II |
Rated insulation voltage Ui |
300 V AC |
Rated impulse withstand voltage Uimp |
4 kV |
Test voltage |
2 kV (50 Hz) (EN 60439-1) |
Electrical data – Control voltage: S11, S21, S33
Control voltage |
22 V DC (? 17.4 V DC) |
Control current |
40 mA … 100 mA |
Short-circuit current |
? 300 mA, between S33 / S11 and S21 |
Short-circuit protection |
Electronic fuse |
Galvanized decoupling |
? (between A1, A2 and S11, S21, S33) |
Electrical data – Input circuits: S12, S22, S31, S34, S35
Input voltage |
|
HIGH |
17.4 V DC … 26.4 V DC |
LOW |
?3 V DC … 5 V DC |
|
Input current |
|
S12, S22, S31 |
? 100 mA |
S34, S35 |
? 50 mA |
|
Reset time |
|
Manual |
? 40 ms |
Automatic |
? 80 ms |
|
Activation time of reset button |
? 50 ms |
Test pulse width |
? 1,000 ?s |
Test pulse rate |
? 10 Hz |
Cable resistance |
? 35 ? |
Electrical data – Electrical output circuits: 13/14, 23/24, 31/32, 33/34
Response time |
? 25 ms 1) |
Number of enable current (N/O) contacts |
2, relevant for safety |
Number of signalling current (N/C) contacts |
1, not safety-relevant |
Contact type |
Positively driven |
Contact material |
Silver alloy, gold flashed |
Switching voltage |
|
Enable current contact |
10 V AC … 230 V AC |
|
10 V DC … 300 V DC |
Signalling current contact |
10 V AC, 10 V DC … 230 V AC, 300 V DC |
|
Current-carrying capacity per OSSD |
|
Enable current contact |
10 mA … 6 A |
Signalling current contact |
10 mA … 6 A |
Total current |
? 12 A |
|
Usage category |
AC-15/DC-13 (EN 60947-5-1) |
Rated operating current (voltage) |
4 A (230 V AC) 360 switching cycles/h
3 A (230 V AC) 3600 switching cycles/h
4 A (24 V DC) 360 switching cycles/h
2.5 A (24 V DC) 3600 switching cycles/h
|
Switching frequency |
? 3600/h |
Mechanical life (relay contacts) |
1 x 107 switching cycles |
Electrical life (relay contacts) |
2 x 106 switching cycles |
Mechanical data
Dimensions (W x H x D) |
22.5 mm x 114 mm x 96.5 mm |
Weight |
0.21 kg |
Classifications
ECl@ss 5.0 |
27371990 |
ECl@ss 5.1.4 |
27371990 |
ECl@ss 6.0 |
27371819 |
ECl@ss 6.2 |
27371819 |
ECl@ss 7.0 |
27371819 |
ECl@ss 8.0 |
27371819 |
ECl@ss 8.1 |
27371819 |
ECl@ss 9.0 |
27371819 |
ETIM 5.0 |
EC001449 |
ETIM 6.0 |
EC001449 |
UNSPSC 16.0901 |
41113704 |