UE23-2MF2A4

4,660,000

Tên sản phẩm: Safety relays UE23-2MF

Danh mục: sens:Control – safe control solutions

Model: UE23-2MF2A4

ID: 6026147

Nhà sản xuất: SICK

Xuất xứ: DE

Hàng mới 100%, bảo hành 12 tháng theo quy định nhà sản xuất

Cung cấp chứng nhận xuất xứ (CO), chứng nhận chất lượng (CQ) theo yêu cầu khách hàng

Mã: 6026147 Danh mục:

Mô tả sản phẩm

sens:Control – safe control solutions

Safety-related parameters
Safety integrity level SILCL2 (EN 62061)
Category Category 3 (EN ISO 13849)
Performance level PL d (EN ISO 13849)
B10d parameter

5.45 x 104 switching cycles (AC-15, 230 V, I = 3 A)

1.26 x 106 switching cycles (AC-15, 230 V, I = 1.5 A)

5.9 x 106 switching cycles (AC-15, 230 V, I = 0.75 A)

4.35 x 105 switching cycles (DC-13, 24 V, I = 2.5 A)

1 x 107 switching cycles (DC-13, 24 V, I = 0.63 A)

PFHD (mean probability of a dangerous failure per hour) 3.0 x 10-6 (EN ISO 13849)
TM (mission time) 20 years (EN ISO 13849)
Stop category 0 (EN 60204-1)
Interfaces
Connection type Fixed screw terminals
Number of enable current (N/O) contacts 2, relevant for safety
Electrical data – Operating data
Protection class II, safe isolation (EN 50178)
Supply voltage VS A1, A2
115 V AC (98 V AC … 132 V AC)
Power consumption (? 3 VA)
Overvoltage category III
Rated insulation voltage Ui 300 V AC
Rated impulse withstand voltage Uimp 6 kV
Test voltage 3.5 kV (50 Hz) (EN 60439-1)
Electrical data – Control voltage: Y1-Y2-Y3
Control voltage (? 40 V DC)
Control current ? 20 mA
Short-circuit current ? 250 mA
Short-circuit protection PTC resistor
Reset time
Manual ? 70 ms
Automatic ? 600 ms
Galvanized decoupling ?
Electrical data – Electrical output circuits: 13/14, 23/24, 31/32
Response time (? 80 ms) 1)
Number of enable current (N/O) contacts 2, relevant for safety
Number of signalling current (N/C) contacts 1, not safety-relevant
Contact type Positively driven
Contact material Silver alloy, gold flashed
Switching voltage
Enable current contact 10 V … 230 V AC
10 V … 300 V DC
Signalling current contact 10 V AC, 10 V DC … 230 V AC, 300 V DC
Current-carrying capacity per OSSD
Enable current contact 10 mA … 6 A
Signalling current contact 10 mA … 6 A
Total current ? 12 A
Usage category AC-15/DC-13 (EN 60947-5-1)
Rated operating current (voltage)

4 A (230 V AC) 360 switching cycles/h

3 A (230 V AC) 3600 switching cycles/h

4 A (24 V DC) 360 switching cycles/h

2.5 A (24 V DC) 3600 switching cycles/h

Switching frequency ? 3600/h
Mechanical life (relay contacts) 1 x 107 switching cycles
Electrical life (relay contacts) 2 x 106 switching cycles
    1) K1/K2.
Mechanical data
Dimensions (W x H x D) 22.5 mm x 123 mm x 93.5 mm
Weight 0.27 kg
Classifications
ECl@ss 5.0 27371990
ECl@ss 5.1.4 27371990
ECl@ss 6.0 27371819
ECl@ss 6.2 27371819
ECl@ss 7.0 27371819
ECl@ss 8.0 27371819
ECl@ss 8.1 27371819
ECl@ss 9.0 27371819
ETIM 5.0 EC001449
ETIM 6.0 EC001449
UNSPSC 16.0901 41113704