Mô tả sản phẩm
Electrical data |
Frequency AC [Hz] |
47…64 |
Operating voltage tolerance [%] |
15…10 |
Nominal voltage AC [V] |
< 230 |
Input voltage range AC [V] |
100…240 |
Output voltage DC [V] |
24…28 |
Protection class |
I; (IEC 61140) |
Overvoltage protection |
yes; (< 32 DC) |
Output voltage [V] |
adjustable; output voltage to SELV, PELV |
Max. output current at min. output voltage [A] |
40 |
Max. output current at max. output voltage [A] |
34.3 |
Max. output current peak at min. output voltage [A] |
60 |
Max. output current peak at max. output voltage [A] |
51.5 |
Output power (permanent) [W] |
960 |
Output power (peak) [W] |
1440 |
Note on output power (peak) |
if consumption > 4 s the power is automatically reduced to the output power |
|
Power factor (nominal voltage 120 V AC / 60 Hz) |
0.99 |
Power factor (nominal voltage 230 V AC / 50 Hz) |
0.99 |
Power reserve [%] |
50 |
Number of output circuits |
1 |
Max. residual ripple [mV] |
100 |
Switch-on peak current (nominal voltage 120 V AC / 60 Hz) [A] |
17 |
Switch-on peak current (nominal voltage 230 V AC / 50 Hz) [A] |
11 |
Inrush current limitation |
yes |
Efficiency (nominal voltage 120 V AC / 60 Hz) [%] |
93.6 |
Efficiency (nominal voltage 230 V AC / 50 Hz) [%] |
94.6 |
External input protection |
? B-16 A / ? C-16 A |
Derating [W/K] |
24 (60…70 ?C) |
Mains buffering time (nominal voltage 120 V AC / 60 Hz) [ms] |
27 |
Mains buffering time (nominal voltage 230 V AC / 50 Hz) [ms] |
27 |
Input current (nominal voltage 120 V AC / 60 Hz) [A] |
8.6 |
Input current (nominal voltage 230 V AC / 50 Hz) [A] |
4.5 |
Power loss (nominal voltage 120 V AC / 60 Hz) [W] |
65.6 |
Power loss (nominal voltage 230 V AC / 50 Hz) [W] |
54.8 |
Back feeding protection [V] |
35 |
Outputs |
Short-circuit proof |
yes |
Overload protection |
yes |
Overload performance |
Hiccup Mode; In the event of overload / short circuit, the output alternately supplies continuous power for 2 s and then switches off for 17 s. |
Type DC-OK signal |
relay output |
Reliability of the DC OK signal |
60 V DC (0.3 A) / 30 V DC (1 A) / 30 V AC (0.5 A) |
Operating conditions |
Ambient temperature [?C] |
-25…70 |
Note on ambient temperature |
observe the free space for convection (see operating instructions) |
|
Storage temperature [?C] |
-40…85 |
Max. relative air humidity [%] |
95; (IEC 60068-2-30) |
Protection |
IP 20; (EN 60529) |
Degree of soiling |
2; (IEC 62103: conductive soiling not permitted) |
Tests / approvals |
EMC |
EN 61000-6-1 |
|
EN 61000-6-2 |
|
EN 61000-6-3 |
|
EN 61000-6-4 |
|
EN 61000-3-2 |
Class A |
|
Vibration resistance |
IEC 60068-2-6 |
?1,6 mm 2…17,8 Hz / 1 g 17,8…500 Hz |
|
Shock resistance |
IEC 60068-2-27 |
15 g 6 ms / 10 g 11 ms |
|
Power Factor Correction (PFC) |
met |
Mechanical data |
Weight [g] |
2044.5 |
Type of mounting |
rail; (TH35 (EN 60715)) |
Dimensions [mm] |
124 x 126 x 132.6 |
Materials |
steel sheet |
Displays / operating elements |
Display |
DC ok |
1 x LED |
overload |
1 x LED |
|
Remarks |
Remarks |
Series connection of outputs only applies to identical units up to max. 150 V DC overall voltage |
|
Pack quantity |
1 pcs. |
Electrical connection |
Connection |
screw terminals: |
Diagrams and graphs |
block diagram |
|
output characteristics |
|
characteristic curve for degree of efficiency / power loss |
|
characteristic line for derating |
|
characteristic line for mains buffering time |
|