IM30-10BUS-ZU0

3,877,000

Tên sản phẩm: Inductive proximity sensors IM AC

Danh mục: IM Standard

Model: IM30-10BUS-ZU0

ID: 7902126

Nhà sản xuất: SICK

Xuất xứ: RO

Hàng mới 100%, bảo hành 12 tháng theo quy định nhà sản xuất

Cung cấp chứng nhận xuất xứ (CO), chứng nhận chất lượng (CQ) theo yêu cầu khách hàng

Mã: 7902126 Danh mục:

Mô tả sản phẩm

IM Standard

Features
Housing Cylindrical thread design
Housing Standard
Thread size M30 x 1.5
Diameter ? 30 mm
Sensing range Sn 10 mm
Safe sensing range Sa 8.1 mm
Installation type Flush
Switching frequency

25 Hz 1)

30 Hz 2)

Connection type Cable, 2-wire, 2 m
Output function NO
Electrical wiring AC/DC 2-wire
Enclosure rating IP67 3)
    1) AC.2) DC.3) According to EN 60529.
Mechanics/electronics
Supply voltage 20 V AC/DC … 250 V AC/DC
Voltage drop ? 6.5 V AC, ? 6 V DC
Time delay before availability ? 8 ms
Hysteresis 1 % … 15 %
Reproducibility ? 10 % 1) 2) 3)
Temperature drift (of Sr) ? 10 %
EMC

According to EN 60947-5-2

As per EN 55011, class B

Continuous current Ia

? 350 mA 4)

? 250 mA 5)

? 100 mA 6)

Off-state current

? 2.5 mA (AC 250 V)

? 1.3 mA (AC 110 V)

? 0.8 mA (DC 24 V)

Minimum load current ? 5 mA
Short-time withstand current 2.2 A 7)
Cable material PUR/PVC
Conductor size 0.5 mm?
Short-circuit protection ? 8)
Power-up pulse protection ?
Shock and vibration resistance 30 g, 11 ms / 10 … 55 Hz, 1 mm
Ambient operating temperature ?25 ?C … +70 ?C
Housing material Metal, Nickel-plated brass
Sensing face material Plastic, Plastic
Housing length 81 mm
Thread length 59 mm
Tightening torque, max. ? 50 Nm
Items supplied Mounting nut, brass, nickel-plated (2x)
Protection class II
Rated insulation voltage Ui 250 V AC
Usage category

AC-140 9)

DC-13 10)

Contamination rating 3
Rated impulse withstand voltage 4 kV
    1) Ub and Ta constant.2) Of Sr.3) Repeatability (Ta not constant).4) AC (+50 ?C).5) AC (+80 ?C).6) DC.7) 20 ms / 0.5 Hz.8) Miniature fuse to IEC 60217-2 Sheet 1, ? 2 A (quick-blow).9) Control of small electromagnetic loads with holding currents < 200 mA.10) Control of solenoids.
Reduction factors
Note The values are reference values which may vary
Stainless steel (V2A, 304) Approx. 0.8
Aluminum (Al) Approx. 0.45
Copper (Cu) Approx. 0.4
Installation note
Remark Associated graphic see “Installation”
A 0 mm
B 30 mm
C 30 mm
D 30 mm
E 0 mm
F 80 mm
Classifications
ECl@ss 5.0 27270101
ECl@ss 5.1.4 27270101
ECl@ss 6.0 27270101
ECl@ss 6.2 27270101
ECl@ss 7.0 27270101
ECl@ss 8.0 27270101
ECl@ss 8.1 27270101
ECl@ss 9.0 27270101
ETIM 5.0 EC002714
ETIM 6.0 EC002714
UNSPSC 16.0901 39122230